Tools for Electricians and Plumbers

Six sizing checks that do the arithmetic around a code table without pretending to be one. You read the value out of the edition your jurisdiction has actually adopted; these pages do the derating, the counting and the budgeting that sit on either side of it — in your browser, with nothing sent anywhere.

Conductor Ampacity & DeratingAmbient correction, bundling adjustment and the 110.14(C) termination limit applied to an ampacity you read out of your own book — including the cap that turns 90°C wire into 75°C ampacity.Start hereBox FillDevices count twice, all the grounds count once between them, and pigtails count for nothing. The counting rules are where box fill goes wrong; the volumes are yours.OpenMotor Circuit SizingConductors size from the code table, overload sizes from the nameplate. Two sources on purpose, and swapping them is the classic error.OpenWater Supply SizingFixture units with flushometers kept apart from tanks, a velocity check, and the pressure budget from street to highest fixture — where only friction responds to a bigger pipe.OpenDrainage Fixture UnitsThe same nominal size carries less horizontally than vertically, so branch and stack are checked separately against capacities you supply.OpenGas Pipe SizingThe longest-length method done the right way round: one governing length for every segment, and each segment carrying everything downstream of it.Open

Why the tables are not in here

It would be easy to embed an ampacity table, a fixture unit list and a gas capacity chart, and it would make every one of these pages a single box you type a load into. We have not, and the reason is not caution for its own sake.

A code table is only correct in the context of an edition, a jurisdiction and whatever local amendments have been made to it. A number typed into a web page has none of that context, does not change when your council adopts a new cycle, and gives no sign when it has gone stale. The failure mode is silent and the consequence is a conductor, a drain or a gas line sized against a rule that is no longer in force.

So the lookup stays with you and your book, where the context lives. What these pages take on is the part that is genuinely arithmetic — and, as it happens, the part that most of the errors are actually in. Nobody misreads 310.16. People forget the termination limit, apply one derating factor and not the other, count a device once, or size a gas segment on its own length.

One thing that turned out to be a formula

While building these we checked whether the ambient temperature correction factors really need a table. They do not. The published figures are computed from √((Tc − Ta) ÷ (Tc − 30)), and deriving it reproduces every printed value to the two decimals the table carries. So that one is calculated rather than looked up — which also means it answers for ambients between the printed rows instead of making you round to the nearest one. Where something is a formula, we would rather derive it than transcribe it. Where it is genuinely a table, it stays in your book.

What is deliberately not here

No code tables. No ampacity values, no fixture unit lists, no gas capacities, no volume allowances. Every one of those is an input you supply from your own adopted edition.

No determination of compliance. These pages check arithmetic against figures you entered. They do not know your edition, your local amendments, or your job. A licensed professional and the authority having jurisdiction decide compliance, and where they or the published code differ from anything here, they are right.

No load calculations, vent sizing or short-circuit protection. Dwelling load calculations, vent tables, and the 430.52 percentages for motor short-circuit protection are each their own body of rules, and a page that gestured at them would do more harm than leaving them out.

Nothing sent anywhere. Every figure you type stays in your browser. Nothing is uploaded, stored on a server, or included in analytics.